By now you should have seen the blue notices hanging in your stairwells or on your doors. The recent power outages at 41 Chatham, 27 and 29 Irving were caused by too many air conditioners being used at one time.
Peter Grasso from Grasso Electric came out to look at our current electrical system (100 Amp/3 Phase) this past week.
Looking at the array of meters, we have 4 Vertical Banks with 4 Breakers at the bottom of each Bank. We have 3 legs of power feeding in from the 100 Amps, Leg A, B & C.
- The first Bank on the left is being fed by Legs A & B.
- The next Bank is fed by Legs B & C.
- The next Bank is fed by Legs A & C.
- The far right Bank is fed by Legs A & B.
Bottom line.....Only 2 Banks were being fed by Leg C.
Peter moved some of the loads off of Leg A to Leg C (Stacks at 29 Irving/4th floor, 29 Irving/3rd floor and 27 Irving/1st floor.)
Peter moved some of the loads off of Leg A to Leg C (Stacks at 29 Irving/4th floor, 29 Irving/3rd floor and 27 Irving/1st floor.)
Peter said that this is the best balance he can provide, based on the measurements. It could get you through the summer but recommended that residents would need to cut back on the A/C.
We understand that it is hot, but ask that you be considerate of your neighbors and cut back on the A/C usage.
The board has asked Wellington Property Management to look into an analysis to bring in more power. More than likely we will need to get approval from National Grid to bring in more power and this could be a lengthy process.
The board plans on discussing this more at our next meeting on July 27,2010.
We understand that it is hot, but ask that you be considerate of your neighbors and cut back on the A/C usage.
The board has asked Wellington Property Management to look into an analysis to bring in more power. More than likely we will need to get approval from National Grid to bring in more power and this could be a lengthy process.
The board plans on discussing this more at our next meeting on July 27,2010.